Wolf FB363 Betriebsanleitung Seite 24

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 60
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 23
3062449_030924
Commissioning
Programming the following components
1. Wolf boiler control unit COB, Wolf control unit for wall mounted
boilers and MGK standard control unit
Set parameter HG22 (maximum boiler temperature) =
parameter KM03 (maximum header temperature) to + 5 K.
2. BM programming module
Set parameters such as time, day, time programs, etc.
3. Extension modules KM, MM and SM
Match the parameters to the specic requirements.
Start the system again via the system ON/OFF switch (mains "OFF/
ON"). The system is ready to operate after approx. 3 min.
Step 7
Step 8
After the successful commissioning, the number of boilers appears on the BM below the current
time.
Conguration Wolf boiler control unit COB
Parameter HG06 (pump operating mode): Select pump operating
mode 1 in conjunction with Wolf boiler control unit COB.
HG06 = First description see COB control unit manual.
Note: Parameter HG06 must not be changed for Wolf control units
for wall mounted boilers and MGK standard control units.
Step 6
Seitenansicht 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 59 60

Kommentare zu diesen Handbüchern

Keine Kommentare