Electrical connection
Note: During service work, isolate the entire system from the power
supply, otherwise there will be a risk of electrocution.
Maximum thermostat When connecting the maximum thermostat at the "Max TH"
terminals of the KM, only the mixer circuit pump will be stopped
in case of faults (mixer no longer closes).
Without a maximum thermostat, extremely high temperatures may
occur in the under oor heating circuit, should the KM develop a
fault. This can result in the oor developing cracks. If with the
con gurations 1, 2, 3, 4, 5, 7, 8 and 13 no maximum thermostat is
connected, plug a 3-pole Rast5 plug with jumper in its place.
Fault message input With all con gurations except con guration 5, the grey 2-pole
plug with jumper must be plugged into input "E2" if the fault input
is not used.
Outside temperature
sensor
There are four options for integrating an outside temperature
sensor into a system:
a) Outside temperature sensor at boiler 1 (address 1) at terminal
AF, part no. 2792021.
b) Outside temperature sensor at BM (address 0) in the wall
mounted base at terminal 5/6, part no. 2792021.
c) Radio clock module with outside temperature sensor connected
to the eBUS, part no. 2792325.
d) Wireless outside temperature sensor and radio receiver
connected to the eBUS, part no. 2744081 and 2744209.
Recommended cables
and minimum cable
cross-sections:
H05VV 3x1.0 mm² power cable
H05VV 3x0.75 mm² mixer circuit pump
H05VV 3x0.75 mm² max. thermostat, three-way diverter valve
H05VV 4x0.75 mm² mixer motor
H05VV 2x0.5 mm² BUS cable