A blocking time is provided that prevents further boilers/heating
stages from being started, to prevent boilers/heating stages
frequently cycling ON and OFF. An additional boiler/burner
stage can only be started after the blocking time has expired.
This blocking time does not apply to the lead boiler, if there is a
DHW demand or convector heater demand from the cascade or
mixer modules.
KM 07 Blocking time
After the adjustable burner hours run gure has expired, the
current lead boiler changes, if parameter
KM 08 "Setting C"
has been selected, the boiler sequence between A and b;
when "Setting d" has been selected, the next boiler in rotation
becomes the lead boiler. That boiler is lead boiler, whose
cascade module is switched ON rst in the cascade and is shut
down last. Precondition for an automatic changeover of boiler
sequence is the selection of a boiler sequence (parameter
KM 12) = C or d.
The internal hours run meter for the boiler sequence
changeover is saved daily (0:00 h) to a non-volatile memory.
The last value saved is downloaded in case of power failure.
Any reset at the KM (= loading standard values) returns the
internal hour count to zero.
KM 08 Hours until a
boiler sequence change
Setting the P portion of the PI controller for header temperature.
Parameter value
km 09 increase ⇒
header temperature control responds more slowly
Parameter value km 09 reduce ⇒
Header temperature control responds more quickly
KM 09 1/Kp header
temperature control
start
Setting the P portion of the PI controller for header temperature.
For a description, see parameter
km 09
KM 10 1/Kp Header
temperature control
stop
Setting the I portion of the PI controller for header temperature.
Parameter value
km 11 increase ⇒
header temperature control responds more slowly
Parameter value km 11 reduce ⇒
header temperature control responds more quickly
KM 11 Tn Header
temperature control
The "Maximum ow temperature" parameter limits the set
header temperature of the heating circuits (mixer circuits and
direct heating circuits) upwards. Parameter
km 03 takes priority.
KM 04 Maximum
ow temperature
The "Minimum header temperature" parameter limits the set
header temperature downwards.
KM 05 Minimum
ow temperature
If only one boiler/burner stage is still in operation, that boiler/
burner stage will be shut down if the following applies: Actual
header temperature > set header temperature + hysteresis.
KM 06 Hysteresis
header temperature
Parameters / Function description