Setting the eBUS address of the extension
and programming modules (KM, MM, BM)
Setting the eBUS address
of the extension and
programming modules
(KM, MM and BM)
The address of the cascade module KM remains set to 1 (factory
setting). In addition to the KM, up to six mixer modules MM can be
connected to a single system. The MM addresses are assigned
in sequence from 2 to 7 in conjunction with the Wolf control unit
for wall mounted boilers, MGK standard control unit or the Wolf
boiler control unit COB.
The functions of each cascade module and each mixer module
are determined via the con guration settings (see also "Electrical
connection").
Each system can comprise up to seven mixer circuits and one
direct heating circuit. Consequently, con guration 3 or 9 may
only be assigned once per system, irrespective of whether in the
cascade or mixer module.
In addition to each mixer module (mixer circuit) one BM programming
module can be used to provide full control.
The direct heating circuit is always regulated by the programming
module with address 0.
2 MM
3 MM
4 MM
5 MM
MK 7
6 MM BM
1 MM BM
KM BMBM
option
option
option
MK 2
MK 1
HC
Wolf
boiler
a) max. expansion with Wolf control unit for wall mounted boilers,
MGK standard controller or Wolf boiler control unit COB
The KM can also be used as stand-alone mixer circuit controller,
if no boiler is installed. For this, either an outside temperature
sensor must be connected to the BM (0) or a DCF receiver with
outside temperature sensor must be connected to the eBUS; see
also "Electrical connection/outside temperature sensor". The KM,
MM and BM addresses are set in accordance with the scheme
including Wolf boilers.
Display example:
BM (factory setting)
Address 0
Address 2
Address 3
Address 4
Address 5
Address 6
Address 7
Address 1 (factory setting)
Setting the eBus