See "MI 15 = dTOFF (stop differential)"
MI 16 dTEin
(start differential)
Conguration
km 01 = 5
Conguration 5 comprises a mixer circuit control and a dT control
for central heating backup. Condition for central heating backup,
see parameter description mi 18.
Output 1 ON, if PF_ist > RLF_ist + dTEin
Output 1 OFF, if PF_ist < RL_ist + dTAus
MI 15 dTAus
(stop differential)
For starting the primary pump, cylinder primary pump
(conguration 1, 4 and 10)
Or for ext. heat demand (conguration 2 and 11),
we differentiate between two cases:
a) Par.
MI 12 = 0: The primary pump is started immediately after
the demand is issued.
b1) Par. MI 12 = 1 with conguration 1, 4 and 10:
Primary pump "ON": Primary pump “ON”: actual header
temperature > actual cylinder temperature + 5 K
Primary pump "OFF": Actual header temperature ≤
actual cylinder temperature + 2 K
b2) Par. MI 12 = 1 with conguration 2 and 11:
Primary pump "ON": Primary pump “ON”: Actual header
temperature > Constant temperature - 5K
Primary pump "OFF": Primary pump “OFF”: Actual header
temperature > Constant temperature - 8 K
MI 12 Primary pump block
The primary pump run-on starts after cylinder heating or ext. heat
demand has been terminated (conguration 1, 2, 4, 10 and 11).
MI 13 Primary pump
run-on time
The system regulates to the selected set ow temperature, and
output A1 is regulated in case of an external heat demand via a
zero volt contact at input E1 and parameter conguration = 2 or 11.
External heat demand takes priority over any heat demand from
the heating circuits. The primary pump run-on starts after the
external heat demand has terminated. The program selector and
time slot heating or DHW have no inuence.
MI 14 Constant
temperature
Parameters / Function description