Wolf FB363 Betriebsanleitung Seite 53

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 60
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 52
3062449_0309 53
Fault codes
When KM recognises a fault, the red LED ashes and the cascade module fault code is displayed
on the associated BM as well as on the central BM (address 0). The following KM faults are
transmitted via the BUS and are displayed.
Fault code Description Cause Remedy
FC52 Maximum
DHW cylinder
heating time
Max. cylinder heating time
exceeded
See parameter description
MI09
FC78 Header sensor faulty
(terminal SAF)
Faulty sensor or lead Check sensor and lead;
replace, if required
FC70 Mixer circuit or
return sensor faulty
(terminal VF)
Faulty sensor or lead Check sensor and lead;
replace, if required
FC71 Cylinder, buffer,
return or boiler
sensor faulty
(terminal E1)
Faulty sensor or lead Check sensor and lead;
replace, if required
FC79 Fault message input
open or return sensor
faulty (terminal E2)
Fault message input open
Faulty sensor or lead
If the fault message input
does not receive a signal,
insert the grey 2-pole plug
with jumper.
Check sensor and lead;
replace, if required
FC81 EEPROM fault Parameter value outside
valid range
Reset to standard values.
Briey interrupt the power
supply and check settings
FC91 BUS address Two or more accessory
controllers share the same
BUS address
Check address settings
--- Mixer circuit pump is
not controlled
Maximum thermostat has
responded (excessive ow
temperature) or three-
pole plug with jumper has
not been set (replaces
maximum thermostat)
Wait until the ow
temperature has cooled
down or insert three-pole
plug with jumper
Seitenansicht 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 59 60

Kommentare zu diesen Handbüchern

Keine Kommentare